1.3 Parameter Table
74
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
o3: Copy Function
o3-01
(515H)
Copy Function
Selection
0: No action
1: Read parameters from the drive, saving them onto the digital operator.
2: Copy parameters from the digital operator, writing them to the drive.
3: Verify parameter settings on the drive to check if they match the data
saved on the operator.
Default: 0
Min: 0
Max: 3
o3-02
(516H)
Copy Allowed
Selection
0: Read operation prohibited
1: Read operation allowed
Default: 0
Min: 0
Max: 1
o4: Maintenance Monitor Settings
o4-01
(50BH)
Cumulative
Operation Time
Setting
Sets the value for the cumulative operation time of the drive in units of 10 h.
Default: 0
Min: 0
Max: 9999
o4-02
(50CH)
Cumulative
Operation Time
Selection
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation
time).
Default: 0
Min: 0
Max: 1
o4-11
(510H)
U2, U3 Initialization
0: U2-
and U3-
monitor data is not reset when the drive is initialized
(A1-03).
1: U2-
and U3-
monitor data is reset when the drive is initialized
(A1-03).
Default: 0
Min: 0
Max: 1
o4-12
(512H)
kWh Monitor
Initialization
0: U4-10 and U4-11 monitor data is not reset when the drive is initialized
(A1-03).
1: U4-10 and U4-11 monitor data is reset when the drive is initialized
(A1-03).
Default: 0
Min: 0
Max: 1
o4-13
(528H)
Number of Run
Commands Counter
Initialization
0: Number of Run commands counter is not reset when the drive is
initialized (A1-03).
1: Number of Run commands counter is reset when the drive is initialized
(A1-03).
Default: 0
Min: 0
Max: 1
o4-20
(3090H)
Event Log
Initialization
0: Event log data is not reset when the drive is initialized (A1-03).
1: Event log data is reset when the drive is initialized (A1-03).
Default: 0
Min: 0
Max: 1
o4-21
(3091H)
Trace Initialization
0: Trace data is not reset when the drive is initialized (A1-03).
1: Trace data is reset when the drive is initialized (A1-03).
Default: 0
Min: 0
Max: 1
<6> Default setting is determined by o2-04, Drive Model Selection.
<10> Default setting is determined by A1-02, Control Method Selection.
<36> Default setting is determined by o1-03, Frequency Reference Selection/Display Unit Setting.
No.
(Addr.)
Name
Description
Setting
Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 74 ページ 2013年10月11日 金曜日 午後8時18分