TOEP C710687 03B FSDrive-MV1000 Parameter Guide
1.3 Parameter Table
1.3 Parameter Table
u
A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
No.
(Addr.)
Name
Description
Setting
Page
A1: Initialization Parameters
A1-00
(100H)
Language Selection
0: English
1: Japanese
7: Chinese (Available from the drive software version S0106 and later.)
11: Polish (Available from the drive software version S0105 and later.)
Default: 1
Min: 0
Max: 11
A1-01
(101H)
Access Level
Selection
0: View and set A1-00, A1-01, and A1-04. U
-
parameters can also be
viewed.
1: User Parameters (access to a set of parameters selected by the user, A2-01
to A2-32)
2: Advanced Access (access to view and set all parameters)
Default: 2
Min: 0
Max: 2
A1-02
(102H)
Control Method
Selection
0: V/f Control
2: Open Loop Vector Control
3: Closed Loop Vector Control
Default: 2
Min: 0
Max: 3
A1-03
(103H)
Initialize Parameters
0: No initialization
1110: User Initialize (parameter values must be stored using parameter
o2-03)
2220: 2-wire initialization (Resets all parameters to default values.)
Default: 0
Min: 0
Max: 2220
A1-04
(104H)
Password
When the value set in A1-04 does not match the value set in A1-04,
parameters A1-01 through A1-03, A1-06, and A2-01 through A2-32 cannot
be changed.
Default: 0
Min: 0
Max: 9999
A1-06
(127H)
Application Preset
0: Disabled
Note:
This function is not available. Always set this parameter
to the default value of 0 (disabled).
Default: 0
A1-90
(3000H)
Year Setting
Sets the year for the calendar. The setting is used for recording event log data
and trace data.
Note:
Some error arises, so periodic adjustment is advisable.
Default: 2011
Min: 2000
Max: 2099
A1-91
(3001H)
Month and Date
Setting
Sets the month and day for the calendar. The setting is used for recording
event log data and trace data.
Note:
Some error arises, so periodic adjustment is advisable.
Default: 1.01
Min: 1.01
Max: 12.31
A1-92
(3002H)
Hour and Minute
Setting
Sets the hour and minute for the calendar. The setting is used for recording
event log data and trace data.
Note:
Some error arises, so periodic adjustment is advisable.
Default: 0.00
Min: 0.00
Max: 23.59
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 24 ページ 2013年10月11日 金曜日 午後8時18分