2.2 b: Application
102
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
n
b1-02: Run Command Selection 1
Determines the Run command source 1 in the REMOTE mode.
Setting 0: Operator
This setting requires entering the Run command via the digital operator RUN key and also illuminates the LO/RE
indicator on the digital operator.
Setting 1: Control Circuit Terminal
This setting requires entering the Run and Stop commands from the contact input terminals using one of the following
sequences:
• 2-wire sequence 1:
Two inputs (FWD/Stop-REV/Stop). Set A1-03 to 2220 to initialize the drive and assign the Forward Run Command
(2-wire Sequence) function (H1-
= 40) to contact input 2. At this time, the Reverse Run Command (2-wire
Sequence) function (H1-
= 41) is not assigned and must be set separately. This is the default setting of the drive.
Refer to Setting 40, 41: Forward Run, Reverse Run Command for 2-Wire Sequence on page 178
• 2-wire sequence 2:
Two inputs (Start/Stop-FWD/REV). Also refer to
Setting 42, 43: Run and Direction Command 2 for 2-Wire
.
Setting 2: MEMOBUS/Modbus Communications
This setting requires entering the Run command via serial communications by connecting the RS-485 serial
communication cable to control terminals R+, R-, S+, and S- on the removable terminal block. For instructions, refer to
the FSDrive-MV1000 Instructions (Manual No. TOEP C710687 02).
Setting 3: Option card
This setting requires entering the Run command via the communications option board by plugging in a communication
option board into the CN5-A port on the control PCB. Refer to the manual supplied with the option board for instructions
on integrating the drive into the communication system.
Note:
If b1-02 is set to 3, but an option board is not installed in CN5-A, an oPE05 operator programming error will be displayed on the
digital operator and the drive will not run.
No.
Name
Setting Range
Default
b1-02
Run Command Selection 1
0 to 3
1