1.3 Parameter Table
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
59
62
Inrush Current Suppression
Circuit Fault
Open: The inrush current suppression circuit fault has been detected.
Note:
This setting is available from the drive software versions S0109 and later.
100 to 160
Function 0 to 60 with Inverse
Output
Inverts the output switching of the contact output functions.
Set the last two digits of 1
to reverse the output signal of that specific function.
Example: 108: Reverses the output of 8 (During Baseblock)
14C: Reverses the output of 4C (During Fast Stop)
No.
(Addr.)
Name
Description
Setting
Page
H3: Analog Inputs
H3-01
(410H)
Analog Input 1
Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min: 0
Max: 1
H3-02
(434H)
Analog Input 1
Function Selection
Sets the function of analog input 1.
Default: 0
Min: 0
Max: FF
H3-03
(411H)
Analog Input 1 Gain Sets the level of the input value selected in H3-02 when 10 V is input at
analog input 1.
Default: 100.0%
Min: -999.9%
Max: 999.9%
H3-04
(412H)
Analog Input 1 Bias Sets the level of the input value selected in H3-02 when 0 V is input at
analog input 1.
Default: 0.0%
Min: -999.9%
Max: 999.9%
H3-09
(417H)
Analog Input 2
Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Default: 1
Min: 0
Max: 1
H3-10
(418H)
Analog Input 2
Function Selection
Sets the function of analog input 2.
Default: 0
Min: 0
Max: 32
H3-11
(419H)
Analog Input 2 Gain Sets the reference value for the function assigned for analog input 2 in %
units when 10 V is input.
Default: 100.0%
Min: -999.9%
Max: 999.9%
H3-12
(41AH)
Analog Input 2 Bias Sets the amount of bias for the function assigned for analog input 2 in %
units when 0 V is input.
Default: 0.0%
Min: -999.9%
Max: 999.9%
H3-13
(41BH)
Analog Input Filter
Time Constant
Sets a primary delay filter time constant for analog inputs 1 and 2. Used for
noise filtering.
Default: 0.03 s
Min: 0.00 s
Max: 2.00 s
H3-14
(41CH)
Analog Input
Terminal Enable
Selection
Determines which analog input terminals will be enabled when the analog
input is set for “PID target value” (H3-
= C).
1: Analog input 1 only
2: Analog input 2 only
3: Analog inputs 1 and 2 only
Default: 3
Min: 1
Max: 3
H3-16
(2F0H)
Analog input 1
Offset
Adds an offset when the analog signal to analog input 1 is at 0 V.
Default: 0
Min: -500
Max: 500
H3-17
(2F1H)
Analog input 2
Offset
Adds an offset when the analog signal to analog input 2 is at 0 V.
Default: 0
Min: -500
Max: 500
H2 Contact Output Settings
H2-
Setting
Function
Description
Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 59 ページ 2013年10月11日 金曜日 午後8時18分