1.3 Parameter Table
58
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
2F
Maintenance Period
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may
require maintenance.
30
During Torque Limit
Closed: When the torque limit has been reached.
31
During Speed Limit
Closed: Speed limit has been reached.
32
During Speed Limit in Torque
Control
Closed: Speed limit has been reached while using Torque Control.
37
During Frequency Output
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial
Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not
being performed).
38
Drive Enabled
Closed: Contact input set for “Drive enable” is closed (H1-
= 6A)
39
Watt Hour Pulse Output
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the
kWh count.
3A
Cooling Fan, Transformer
Abnormal Temperature
Rise
Closed: No abnormal temperature rise in the cooling fans or transformers has occurred.
3C
LOCAL/REMOTE Status
Open: REMOTE
Closed: LOCAL
3D
During Speed Search
Closed: Speed Search is being executed.
3E
PID Feedback Low
Closed: PID feedback level is too low.
3F
PID Feedback High
Closed: The PID feedback level is too high.
40
Close Command for
Commercial Power Supply
Side Breaker
Open: Open Command
Closed: Close Command
Note:
Use this setting if the Synchronous Transfer is used.
41
Close Command for Drive
Secondary Side Breaker
Open: Open Command
Closed: Close Command
Note:
Use this setting if the Synchronous Transfer is used.
42
Completion Signal for
Synchronous Transfer
Open: The Synchronous Transfer is in progress or it is not used.
Closed: The Synchronous Transfer to commercial power supply completed.
Note:
Use this setting if the Synchronous Transfer is used.
4C
During Fast Stop
Closed: A Fast Stop command has been entered from the operator or input terminals.
4D
oH Pre-Alarm Time Limit
Closed: oH pre-alarm time limit has passed.
60
Internal Cooling Fan Alarm
Closed: Internal cooling fan alarm
H2 Contact Output Settings
H2-
Setting
Function
Description
Page
All Modes
common_
CLV
V/f
OLV
common
CLV
V/f
OLV
common
CLV
V/f
OLV
common
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 58 ページ 2013年10月11日 金曜日 午後8時18分