1.3 Parameter Table
38
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
d5-06
(29FH)
Speed/Torque
Control Switchover
Time
Sets the delay time for switching between Speed and Torque Control using
an input terminal (H1-
= 71).
Within the time set for the speed/torque control switching timer, analog
inputs (torque reference, speed limit values) are held at their value at the
moment of the “speed/torque control switching” change. Complete the
preparations for switching externally during this period.
Default: 0 ms
Min: 0 ms
Max: 1000 ms
d5-08
(2B5H)
Unidirectional
Speed Limit Bias
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
d6: Field Weakening and Field Forcing
d6-01
(2A0H)
Field Weakening
Level
Sets the drive output voltage for the Field Weakening function as a
percentage of the maximum output voltage.
Enabled when a contact input is set for Field Weakening (H1-
= 63).
Default: 80%
Min: 0%
Max: 100%
d6-02
(2A1H)
Field Weakening
Frequency Limit
Sets the lower limit of the frequency range where Field Weakening control is
valid.
The Field Weakening command is valid only at frequencies above this
setting and only when the output frequency matches the frequency reference
(speed agree).
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
d6-03
(2A2H)
Field Forcing
Selection
0: Disabled
1: Enabled
Default: 0
Min: 0
Max: 1
d6-06
(2A5H)
Field Forcing Limit Sets the upper limit of the excitation current command during magnetic field
forcing. A setting of 100% is equal to motor no-load current. Disabled only
during DC Injection Braking.
Default: 200%
Min: 100%
Max: 400%
d7: Offset Frequency
d7-01
(2B2H)
Offset Frequency 1
Added to the frequency reference when the contact input “Offset Frequency
1” (H1-
= 44) is switched on. Set as a percentage of the maximum
output frequency.
Default: 0.0%
Min: -100.0%
Max: 100.0%
d7-02
(2B3H)
Offset Frequency 2
Added to the frequency reference when the contact input “Offset Frequency
2” (H1-
= 45) is switched on. Set as a percentage of the maximum
output frequency.
Default: 0.0%
Min: -100.0%
Max: 100.0%
d7-03
(2B4H)
Offset Frequency 3
Added to the frequency reference when the contact input “Offset Frequency
3” (H1-
= 46) is switched on. Set as a percentage of the maximum
output frequency.
Default: 0.0%
Min: -100.0%
Max: 100%
<10> Default setting is determined by A1-02, Control Method Selection.
<20> Range upper limit is determined by d2-01, Frequency Reference Upper Limit, and E1-04, Maximum Output Frequency.
No.
(Addr.)
Name
Description
Setting
Page
CLV
V/f
OLV
common
CLV
V/f
OLV
common
CLV
V/f
OLV
common
CLV
V/f
OLV
common
CLV
V/f
OLV
common
CLV
V/f
OLV
common
All Modes
common_
All Modes
common_
All Modes
common_