1.3 Parameter Table
52
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
14
Fault Reset
Closed: Resets faults if the cause is cleared and the Run command is removed.
15
Fast Stop (N.O.)
Closed: Decelerates at the Fast Stop time set to C1-09.
16
Motor 2 Selection
Open: Motor 1
Closed: Motor 2
17
Fast Stop (N.C.)
Open: Decelerates to stop at the Fast Stop time set to C1-09.
18
Timer Function Input
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction
with the timer function output (H2-
= 12).
19
PID Disable
Open: PID control enabled
Closed: PID control disabled
1A
Accel/Decel Time Selection 2 Used in conjunction with an input terminal set for “Accel/decel time selection 1”
(H1-
= 7), and allows the drive to switch between accel/decel times 3 and 4.
1B
Program Lockout
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned
to the digital operator).
Closed: Parameters can be edited and saved.
1E
Reference Sample Hold
Closed: Samples the analog frequency reference and operates the drive at that speed.
20 to 2F
External Fault
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
30
PID Integral Reset
Closed: Resets the PID control integral value.
31
PID Integral Hold
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
32
Multi-Step Speed Reference 4 The values set in d1-01 to d1-16 (frequency references) can be selected according to the
combination of the four terminals set for Multi-Step Speed References 1 to 4.
33
Thermostatic Switch (N.C.)
Closed: Closes when thermostatic switches are OFF, and then a TME2 (Transformer
Temperature DI Fault) fault occurs.
H1 Contact Input Selections
H1-
Setting
Function
Description
Reference
Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 52 ページ 2013年10月11日 金曜日 午後8時18分