2.2 b: Application
104
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
DC Injection Braking time is determined by the value set to b2-04 and by the output frequency at the time the Stop
command is input or the Run command is removed. It can be calculated by:
Figure 2.3
Figure 2.3 DC Injection Braking Time Depending on Output Frequency
Note:
If an overcurrent (OC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the
fault no longer occurs.
Setting 3: Coast to Stop with Timer
When a Stop command is input or the Run command is removed, the drive will turn off its output and the motor will
coast to a stop. The drive will not start if a Run command is input before the time t (C1-02) has expired. Cycle the Run
command that was activated during time t after t has expired to start the drive.
Figure 2.4
Figure 2.4 Coast to Stop with Timer
The wait time t is determined by the output frequency when the Stop command is input or the Run command is removed
and by the active deceleration time.
Figure 2.5
Figure 2.5 Run Wait Time Depending on Output Frequency
DC Injection brake time
(b2-04)
×
10
×
Output frequency
Max. output frequency (E1-04)
=
Output frequency when
Stop command was entered
100%
(Maximum output
frequency)
10%
DC Injection braking time
b2-04
10
b2-04
Drive output shut off
Run wait time t
Run command
Output
frequency
ON
ON
ON
OFF
OFF
Min output
frequency
100%
(Max output
frequency)
Output frequency
when Stop command
was entered
Run wait time t
Active deceleration time
Min Baseblock Time (L2-03)
MV1000ParameterGuide_E_conditional.book 104 ページ 2013年10月11日 金曜日 午後8時18分