2.7 H: Terminal Functions
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
181
Setting 80: Synchronous Transfer Command from Drive to Commercial Power Supply
Use this setting if the Synchronous Transfer from a commercial power supply to the drive is used.
When a contact input terminal set to 80 closes, Synchronous Transfer from a commercial power supply to the drive is
enabled.
Note:
This function cannot be used simultaneously with settings 80 and 81. If switching between settings 80 and 81, set the active one
to be disabled before setting the other one to be enabled.
Setting 81: Synchronous Transfer Command from Commercial Power Supply to Drive
Use this setting if the Synchronous Transfer from a commercial power supply to the drive is used.
When a contact input terminal set to 81 closes, Synchronous Transfer from a commercial power supply to the drive is
enabled.
Note:
This function cannot be used simultaneously with settings 80 and 81. If switching between settings 80 and 81, set the active one
to be disabled before setting the other one to be enabled.
Setting 82: Close Signal for Commercial Power Supply Side Breaker
Use this setting if the Synchronous Transfer is used.
Make sure the contact input terminal set to 82 closes as an answer signal when the commercial power supply side breaker
is closed and opens when the commercial power supply side breaker is open.
Setting 83: Close Signal for Drive Secondary Side Breaker
Use this setting if the Synchronous Transfer is used.
Make sure the contact input terminal set to 83 closes as an answer signal when the drive secondary side breaker is closed
and opens when the drive secondary side breaker is open.
u
H2: Contact Outputs
n
H2-01 to H2-16: Functions for Contact Outputs 1 to 16
The drive has 16 contact output terminals.
lists the functions available for these terminals using H2-01 to
H2-16.
Table 2.26 Contact Output Parameters
No.
<1> The default setting for the drive with software versions S0107 and earlier is 3A.
Name
Setting Range
Default
H2-01
Contact Output 1 Function Selection
0 to 1FF
10E: Function E with Inverse Output
H2-02
Contact Output 2 Function Selection
0 to 1FF
E: Fault
H2-03
Contact Output 3 Function Selection
0 to 1FF
0: During Run
H2-04
Contact Output 4 Function Selection
0 to 1FF
6: Drive Ready
H2-05
Contact Output 5 Function Selection
0 to 1FF
10: Minor Fault
H2-06
Contact Output 6 Function Selection
0 to 1FF
F: Through Mode
H2-07
Contact Output 7 Function Selection
0 to 1FF
F: Through Mode
H2-08
Contact Output 8 Function Selection
0 to 1FF
F: Through Mode
H2-09
Contact Output 9 Function Selection
0 to 1FF
F: Through Mode
H2-10
Contact Output 10 Function Selection
0 to 1FF
F: Through Mode
H2-11
Contact Output 11 Function Selection
0 to 1FF
F: Through Mode
H2-12
Contact Output 12 Function Selection
0 to 1FF
F: Through Mode
H2-13
Contact Output 13 Function Selection
0 to 1FF
F: Through Mode
H2-14
Contact Output 14 Function Selection
0 to 1FF
F: Through Mode
H2-15
Contact Output 15 Function Selection
0 to 1FF
F: Through Mode
H2-16
Contact Output 16 Function Selection
0 to 1FF
F: Through Mode
H2-17
Watt Hour Output Unit Selection
0 to 4
0: 0.1 kWh units
H2-18
Alarm Output Selection
0 to FFFF
1
MV1000ParameterGuide_E_conditional.book 181 ページ 2013年10月11日 金曜日 午後8時18分