1.3 Parameter Table
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
39
u
E: Motor Parameters
No.
(Addr.)
Name
Description
Setting
Page
E1: V/f Pattern for Motor 1
E1-04
(303H)
Maximum Output
Frequency
To set linear V/f characteristics, set the same values for E1-07 and E1-09. In
this case, the setting for E1-08 will be disregarded. Ensure that the four
frequencies are set according to these rules:
E1-09
≤
E1-07
≤
E1-06
≤
E1-11
≤
E1-04
Note that if E1-11 = 0, then both E1-11 and E1-12 are disabled, and the
above conditions do not apply.
Note:
E1-07, E1-08 and E1-10 are available only in the following control
modes: V/f Control, Open Loop Vector.
Default:
Min: 40.0 Hz
Max: 120.0 Hz
E1-05
(304H)
Maximum Voltage
Default:
Min: 0 V
Max: 13000 V
E1-06
(305H)
Base Frequency
Default:
Min: 0.0 Hz
Max: 120.0 Hz
E1-07
(306H)
Middle Output
Frequency
Default:
Min: 0.0 Hz
Max: 120.0 Hz
E1-08
(307H)
Middle Output
Frequency Voltage
Default:
Min: 0 V
Max: 13000 V
E1-09
(308H)
Minimum Output
Frequency
Default:
Min: 0.0 Hz
Max: 120.0 Hz
E1-10
(309H)
Minimum Output
Frequency Voltage
Default:
Min: 0 V
Max: 13000 V
E1-11
(30AH)
Middle Output
Frequency 2
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
E1-12
(30BH)
Middle Output
Frequency Voltage 2
Default: 0 V
Min: 0 V
Max: 13000 V
E1-13
(30CH)
Base Voltage
Default: 0 V
Max: 0 V
Max: 13000 V
E2: Motor 1 Parameters
E2-01
(30EH)
Motor Rated Current Sets the motor nameplate full load current in Amps. Automatically set
during Auto-Tuning.
Default:
Min: 10% of drive
rated current
Max: 200% of
drive rated current
E2-02
(30FH)
Motor Rated Slip
Sets the motor rated slip. Automatically set during Auto-Tuning.
Default:
Min: 0.00 Hz
Max: 20.00 Hz
E2-03
(310H)
Motor No-Load
Current
Sets the no-load current for the motor. Automatically set during
Auto-Tuning.
Default:
Min: 0 A
Max: E2-01
E2-04
(311H)
Number of Motor
Poles
Sets the number of motor poles. Automatically set during Auto-Tuning.
Default: 4
Min: 2
Max: 48
E2-05
(312H)
Motor Line-to-Line
Resistance
Sets the phase-to-phase motor resistance. Automatically set during
Auto-Tuning.
Default:
Min: 0.000
Ω
Max: 65.000
Ω
E2-06
(313H)
Motor Leakage
Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of
motor rated voltage.
Default:
Min: 0.0%
Max: 40.0%
E2-07
(314H)
Motor Iron-Core
Saturation
Coefficient 1
Sets the motor iron saturation coefficient at 50% of magnetic flux.
Automatically set during Auto-Tuning.
Default: 0.50
Min: 0.00
Max: 0.50
All Modes
common_
Output Voltage (V)
Frequency (Hz)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
CLV
V/f
OLV
common
MV1000ParameterGuide_E_conditional.book 39 ページ 2013年10月11日 金曜日 午後8時18分