2 - 12
Electrical Wiring (4)
Selecting the wiring
cable
The recommended wiring cable is a 600 V vinyl sheath electrical wire CVV
(JIS C 3401) with a conductor section of 2 mm
2
, or a twisted cable with an
equivalent or higher capacity.
Shielded wire is recommended for wiring at locations subject to electromag-
netic noise interference.
Select a sheath material suitable for the cable installation environment (con-
sider ambient temperature, corrosive gas, corrosive fluid, etc.).
Run the cable into the terminal block through the conduit connection (G1/2
internal thread, CM20 external thread, Pg13.5 or 1/2NPT internal thread).
An outer diameter of
φ
11 is optimum. (The applicable range of cable outer
diameters is
φ
10 -
φ
12.)
A crimp terminal (M4 screw) with an insulation sleeve is recommended for
the terminal connections.
The maximum length of the wiring cable is 1500 m. However, the maximum
length between converter and detector is 300 m.
Installing the wiring
cable
When installing the cable connecting this product to the control equipment,
the following precautions must be observed.
Notes:
• Run the wiring away from equipment that may cause noise, such
as high-capacity transformers, motors, or power supplies.
DO NOT install the cable in the same tray or duct as other power
cables. Output errors may result.
• Wiring with electrical tube and duct is recommended to keep out water
and protect the wire from external damage.
Also, be sure to use a waterproof gland at the conduit connection.