4 - 53
Setting a 2-stage Flow Rate Alarm
Introduction
A first alarm will be output when the instantaneous percent flow rate exceeds
the preset first high or low limit. A second alarm will be output when the flow
rate exceeds the second high or low limits.
Important
This function can be used when the 2-stage high/low limit alarm is selected in
the contact output function.
Default setting
HI–ALM1, HI–ALM2 +100%
LO–ALM1, LO–ALM2 –100%
Setting range
HI–ALM1, HI–ALM2 –115 - +115%
LO–ALM1, LO–ALM2 –115 - +115%
Open the 2-stage high/low limit
alarm setup screen by follow-
ing the steps to enter the Engi-
neering Mode.
Use the key to move the
cursor to the desired digits.
Use the and keys to
change the numbers.
Touch the key to move the
cursor to the "#".
1
Screen
Procedure
Step
2
3
4
Continued on next page
# LO-ALM1 -100 %
LO-ALM2 -100 %
# LO-ALM1 -100 %
LO-ALM2 -100 %
# LO-ALM1 +020 %
LO-ALM2 +010 %
# LO-ALM1 +020 %
LO-ALM2 +010 %