5 - 3
Checking the Analog Output
Introduction
The analog output can be checked by using the electromagnetic flowmeter as
a constant current generator.
Default setting
Display current output
Setting range
000.0% - 115.0% (the percentage is the ratio of the preset range.)
Open the analog output check
screen by following the steps to
enter the Maintenance Mode.
Touch the key to move the
cursor to the numerical figure
to be checked. In this situation,
the current corresponding to
the percentage of the preset
I.OUT will be output.
1
Screen
Procedure
Step
Using the and keys,
change the percentage to the
desired one. In the example at
right, an analog output of
100% of the range (20 mA) is
output.
Touch the key to move the
cursor to “>.” The analog out-
put will return to the value cor-
responding to the percentage of
the actual flow rate indicated
on the main display.
2
3
4
> OUTPUT CHECK
I. OUT 000 .0 %
> OUTPUT CHECK
I. OUT 000 .0 %
> OUTPUT CHECK
I. OUT 100 .0 %
> OUTPUT CHECK
I. OUT 100 .0 %