4 - 56
Determining the Pulse Output Abnormality Treatment Direction
Introduction
It is possible to determine the pulse output direction when an abnormality
occurs in the electromagnetic flowmeter and flow rate measurement becomes
impossible. Use this function when pulse output is selected.
• The abnormality treatment direction is very important for securing
the safety of the overall control process. Determine the treatment
direction very carefully. Otherwise the equipment will be dam-
aged.
Caution
"LOW"
"LOW":
Outputs no pulse.
"HOLD": Holds the pulse to the value obtaining just before the abnormality
occurred.
Default setting
Setting range
Open the pulse output abnor-
mality treatment direction setup
screen by following the steps to
enter the Engineering Mode.
Touch the key.
Use the or key to deter-
mine the abnormality treat-
ment direction.
Touch the key to move the
cursor to the "#".
1
Screen
Procedure
Step
2
3
4
# ERROR OUT MODE
P. OUT LOW
# ERROR OUT MODE
P. OUT LOW
# ERROR OUT MODE
P. OUT HOLD
# ERROR OUT MODE
P. OUT HOLD