AC70 VC CONTROL FREQUENCY INVERTER MANUAL
FUNCTION PARAMETER DETAILED SPECIFICATION
94
18
Frequency main channel
selection terminal 3
0-11 frequency input channels
19
Frequency main channel
selection terminal 4
20
Program running pause
During the program running, this signal enable
program running to pause. Output frequency will be
0 if this command is activated, continue to run base
on running status before pause if pause signal
disappears.
21 Program
restart
During the program running, if this signal is valid, it
enables the program running to restart, starts to
run from first stage;
22
Timer trigger terminal
Start timer to start timing, refer to in detail
[F-38].
23
Timer reset terminal
Clear the records of the timer
24
Counter reset terminal
Clear the records of the counter
25
Counter clock input terminal
Refer to
[F-39, F-40]
26
Only terminal control channel is enabled
selection
Only terminal control channel is enabled, keypad
and Rs485 command channel is invalid.
27
Forward running
Refer to forward running description in detail.
28
Reverse running
Refer to forward running description in detail.
Acceleration/deceleration time selection reference list.
Terminal 2
Terminal 1
Acceleration/deceleration time selection
OFF
OFF
Acceleration time 1 and deceleration time 1
OFF
ON
Acceleration time 1 and deceleration time 2
ON
OFF
Acceleration time 1 and deceleration time 3
ON
ON
Acceleration time 1 and deceleration time 4
Short connect with
(
COM
)
is “ON”, disconnection is “OFF”
Forward running description:
As the running command given by terminal, and if
[F-08]
set as standard operation
control, when this terminal is valid, inverter runs in forward direction, refer to
[F-08]
parameters for other control
mode function.
Reverse running description:
As the running command given by terminal, and if
[F-08]
set as standard operation
control, when this terminal is valid, inverter runs in reverse direction, refer to
[F-08]
parameters for other control
mode function.
F-07
Input signal respond mode
selection
Range:0000-1121 Default:0001
LED unit digit: Free stop terminal recover mode
0: Recover to original command with speed search function
1: Don’t recover to original command
2: Recover to original command without speed search function, No speed search of this function need to set unit
digit of
[E-30]
for 2 together.