AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW
5
V/F curve
5 kinds curve programmable setting:1 user setting, 1 of linear
characteristic torque curve setting. 3 kinds derating torque
setting( 1.5 power, 1.7 power, 2.0 Power curve )
Accel / Decel. curve
Two kinds curve: line Accel/Decel, S curve Accel/Decel.
4 Aceel/Decel time unit is 0.1s, maximum time 6500.0s
Rated output voltage
Power voltage compensation is available, setting range from 50 to
100%( rated voltage), the output voltage can't over than input
AVR( Auto Voltage Regulation
automatic voltage regulation for keeping output voltage stable when
fluctuation of grid
Auto energy saving running
Optimized the output voltage according the load to achieve energy
saving
Auto current limit
Auto current limit during running mode to avoid trip occurs
frequently
Momentary Power Loss with
no stop running function
To achieve continuous running with regenerative enery and DC bus
voltage regulation when momentary power loss
Standard Function
PID control, Carrier frequency adjustable, current limiter, Speed
Search, Momentary Power Loss restart,8 Step Speed (max), 3-wire
Sequence, Slip Compensation, Frequency Jump, Upper/lower
Limits for Frequency Reference, DC Injection Braking at Start and
Stop, Energy Saving Control, Modbus Comm RS485, Fault Restart,
job function, Cooling Fan on/off Switch, timing stop, high pulse
output, programmable auto running, swing frequency, counter,
frequency arriving detect and frequency lever detect.
Frequency Setting Methods
Keypad digital setting, potentiometer of keypad, analog voltage
terminal VS1, analog voltage terminal VS2, analog current terminal
AS, RS485 communication and multiple terminal, main and auxiliary
composition setting.
Feedback Input Channel
voltage terminal VS1, VS2, current terminal AS, communication ,
and pulse input PUL
Running command channel
keypad given, external terminal given, communication given
Input command signal
Start, Stop, FEW/Reverse, Job, Multiple speed, free stop, Reset,
Accel/Decel time, Frequency set point channel, External fault
Output signal
2 Photo coupler relays: 2 (24 V, up to 50 mA)
1 Contact relays: 1 (250 Vac/up to 1 A, 30 Vdc/up to 1 A)
0-10V output, 4 to 20mA output
Frequency pulse output
Protection function
Overvoltage, under voltage, current limit, over current, overload,
electric thermal relay, overheat, Stall prevention, parameter lock