AC70 VC CONTROL FREQUENCY INVERTER MANUAL
FUNCTION PARAMETER DETAILED SPECIFICATION
105
F-53 Pulse input frequency lower limit Range: 0.0KHz-[F-54] Default: 0.0KHz
F-54
Pulse input frequency upper limit Range:[F-53]-50.0KHz Default:10.0
KHz
F-55
Pulse input frequency gain
Range:
0.01-5.00 Default:
1.00
Terminal input frequency lower limit
This function defines the minimum frequency received by the analog
input terminal (PUL). Frequency inverter will automatically filter the frequency whose value is lower than this value;
Terminal input frequency upper limit
This function defines the maximum frequency received by the analog
input terminal (PUL). Frequency inverter will automatically filter the frequency whose value is higher than this value.
Terminal input frequency gain
This function is used to amplify or reduce the (PUL) terminal input signal.
F-56
Input lower limit correspond
setting frequency
Rang: 0.00Hz-[F-57]
Default: 0.00Hz
F-57
Input upper limit correspond
setting frequency
Range: [F-56]-maximum frequency
Default: 50.00Hz
These two parameters stipulate the corresponding relation between the external input analog value, upper/lower
limit of the pulse signal and frequency.
F-58 Input signal characteristic
selection
Range:0000-1111 Default:0000
LED unit digit: VS1 input characteristic selection
0: Positive characteristic 1: Negative characteristic
LED ten digit: AS input characteristic selection
0: Positive characteristic 1: Negative characteristic
LED hundred digit: VS2 input characteristic selection
0: Positive characteristic 1: Negative characteristic
Tips: When
(
VS2
)
opens bipolar function (
[F-48]
is set as 1 or 2 ), this parameter is invalid.
LED thousand digit: Pulse input characteristic selection
0: Positive characteristic 1: Negative characteristic
When in positive characteristic stage, lower limit of external analog input value and the pulse signal corresponds to
[F-56]
, upper limit of exterior analog input value and the pulse signal corresponds to
[F-57]
.
When in negative characteristic stage, lower limit of exterior analog input value and the pulse signal corresponds to
[F-57]
, upper limit of exterior analog input value and the pulse signal corresponds to
[F-56]
.
As shown in the Fig.
[F-56]
(fmin), the biggest analog input and the pulse signal corresponding frequency setting
means their upper limit value corresponding frequency setting, As shown in the Fig.
[F-57]
(fmax).