AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
24
Y1/Y2
Collector open circuit output, can set the
action-object by program.
DC24V/50mA
TA/TB/TC
Passive connector output
,
can set the action-object
by program.
3A/240VAC
5A/30VDC
Table 3-4:AC70 series inverter auxiliary terminals output capacity
●
Switch terminals connection function specification
Switch
terminal
Optional
position
Picture example
Function specification
(
K2
)
J1
(AO2)
0.0
~
50kHz open collect pole pulse
frequency output
J2
(AO2)
0
~
20mA current output or
4
~
20mA current output
J3
(AO2)
0
~
10V voltage output
(K1)
J4
J4
connect
(AO1)
0
~
10V voltage output
J5
J5
conne
(AO1)
0
~
20mA current output or
4
~
20mA current output
(K3)
J6
J6
conne
RS485 communication initial port
connect matching resistor 120
Ω
J7
J7
conne
Matching resistor disconnect
Table 3-5:AC70 series inverter switch terminal connection function specification