AC70 VC CONTROL FREQUENCY INVERTER MANUAL
APPENDIX
119
Appendix 1: Appendix
9.1 Appendix 1: Function Code Simple List
“
●
”: Stand for this parameter can be modified in running mode.
“
〇
”: Stand for this parameter can not be modified in running mode.
“×”: Stand for this parameter is read only, can’t be modified.
“–”: Stand for factory authority parameters. Veichi setting is available only.
“ ”: Stand for this parameter is related to frequ
※
ency inverter model.
Basic function code group
Code
function
Function name
Setting range and definition
Factory
default
pr
op
ert
y
Refe
r to
page
Comm
unicati
on
code
E-00
Control method selection
0: Open loop vector control without
PG
1: V/F control mode
1
〇
69 100H
E-01
Running control command
channel selection
0: Operator keypad
1: External terminal control
2: RS485 Communications port
control
0
〇
69 101H
E-02
Frequency reference
given main channel
selection
0: Operator keypad digital given
1: Potentiometer of keypad
2: Terminal VS1 analog voltage
0-10V
3: Terminal AS analog current
signal 4-20mA
4: Terminal VS2 analog voltage
-10-10V
5: Pulse train signal
6: RS485 communication port
7: Up and Down control
8: General PID operation
9: Constant pressure PID control
10: Program running
11: Swing frequency run
12: Terminal selection:
1
〇
69 102H
E-03
Frequency reference
given auxiliary channel
selection
0: Operator keypad digital
1: Potentiometer of keypad
2: Terminal VS1 analog voltage
0-10V
3: Terminal AS analog current
signal 4-20mA
4: Terminal VS2 analog voltage
-10-10V
5: Pulse train signal
6: RS485 communication port
7: Up and Down control
8: General PID operation
9: Constant pressure PID control
10: Program running
0
〇
71 103H