AC70 VC CONTROL FREQUENCY INVERTER MANUAL
FUNCTION PARAMETER DETAILED SPECIFICATION
115
6
Reverse; Acceleration time 1/Deceleration time 3
7
Reverse; Acceleration time 1/Deceleration time 4
H-43
1 step speed running time T1
Range: 0.0-6000.0
Default: 10.0
H-44
2 step speed running time T2
Range: 0.0-6000.0
Default: 10.0
H-45
3 step speed running time T3
Range: 0.0-6000.0
Default: 10.0
H-46
4 step speed running time T4
Range: 0.0-6000.0
Default: 10.0
H-47
5 step speed running time T5
Range: 0.0-6000.0
Default: 10.0
H-48
6 step speed running time T6
Range: 0.0-6000.0
Default: 10.0
H-49
7 step speed running time T7
Range: 0.0-6000.0
Default: 10.0
H-50
8 step speed running time T8
Range: 0.0-6000.0
Default: 10.0
Use to set 8 steps speed running time, unit of time is set by
[H-32]
parameters.
H-51
Differential frequency f in swing
△
frequency
Range:0.00Hz-20.00Hz
Default:2.00Hz
During the swing frequency operation, the FOR/REV switching function will be forbidden, running direction is
programmed after stop only. f1 is the setting value of
[F-09]
; f2 is the setting value of
[F-10]
; Acceleration time T1 of
the amplitude is the setting value of
[F-24]
; And the acceleration time T2 of the amplitude is the setting value of
[F-25]
.
The acceleration/deceleration time in swing frequency running is defined by acceleration/deceleration time 1. When
using the swing frequency running function, frequency inverter will run with the acceleration/deceleration time 1 to
the f1 setting frequency, then begin swing frequency running. While stop, frequency inverter will run for
acceleration/deceleration time 1 from the running frequency to stop. Acceleration/deceleration time of the amplitude
is defined by acceleration/deceleration time 2. It is defined as the same as acceleration/deceleration time 1.
The parameter settings in the swing frequency running should satisfy the following formula request, otherwise
display "Err5".
f1>f2+
ᇞ
f
f2
≥
0.50Hz
0
≤
ᇞ
f
≤
20.00Hz
f
Output frequency
acc time 1
runing order
swing frequency running diagram
Time
dec time 1
T2
T1
T2
T1
T2
f
f
f
f
f
swing frequency f1
swing frequency f2
H-52
Motor rated power
Range: 0.4-1100.0KW
Default:
※
H-53
Motor rated frequency
Range: 0-600.00Hz
Default: 50.00Hz