AC70 VC CONTROL FREQUENCY INVERTER MANUAL
FUNCTION PARAMETER DETAILED SPECIFICATION
89
LED unit digit:
0: Null operation
1: State monitoring inquiry
2: Fault information inquiry
0: Null operation
1: State monitoring inquiry Selects this function to enter monitoring menu
(
group C parameters
)
,and inquire
each state parameters of the frequency inverter. In the monitoring state, with long pressing (1 second) PRG key
and enter directly the state of the group C parameters that is status of state monitoring inquiry.
Monitoring
code
Content
Unit
Communication
cod
C-01 Frequency
reference
given
0.01Hz
C01H
C-02 Output
frequency
0.01Hz
C02H
C-03 Output
current
0.1A
C03H
C-04 Input
voltage
V
C04H
C-05 Output
voltage
V
C05H
C-06 Machine
speed
RPM
C06H
C-07
PID given value
%
C07H
C-08
PID feedback value
%
C08H
C-09 Module
temperature
℃
C09H
C-10
Accumulative running time ( the total timing of
output frequency which large than 0Hz, 0Hz
running and stop status timing is disabled )
Hour C0AH
C-11
Accumulative running timing after last power on
Minute
C0BH
C-12
Output current percentage
%
C0CH
C-13
Multi-Step operation remainder time percentage
%
C0DH
C-14
Input terminals OFF/ON status
Refer to below table
C0EH
C-15
Output terminals OFF/ON status
Refer to below table
C0FH
C-16
Terminal VS1 input value
0.1V
C10H
C-17
Terminal AS input value
0.1mA
C11H
C-18
Terminal VS2 input value
0.1V
C12H
C-19
Terminal pulse input value
※
C13H
C-20 Counter
record
※
C14H
C-21
DC bus voltage
V
C15H
C-22 Analog
output
A01
※
C16H
C-23
Frequency/voltage/current outputA02
※
C17H
C-24 Reserve
--
C18H
C-25
Inverter rated power
kW
C19H
C-26
Inverter rated voltage
V
C1AH
C-27
Inverter rated current
0.1A
C1BH
C-28 Software
version
※
C1CH