AC70 VC CONTROL FREQUENCY INVERTER MANUAL
FUNCTION PARAMETER DETAILED SPECIFICATION
108
F-70
UP/DW terminal preset
frequency
Range: 0.00Hz-Maximum frequency Default:0.00Hz
F-71
UP/DW Power-off
memorized frequency
Range: 0.00Hz-Maximum frequency Default:0.00Hz
The starting frequency output when inverter runs in UP/DW control mode. It is enabled only
[F-07]
LED ten digit
has been set for 1 or 2 .
When the
[F-07]
LED ten digit sets for 1,
[F-71]
parameters will memorize the last UP and DOWN control
momentary frequency. User can review and modify the last stop momentary frequency via
[F-71]
in stop status.
When the
[F-07]
LED ten digit sets for 2, the starting frequency can be preset via
[F-70]
parameters in UP/DW
control.
8.3. Special Function Parameters
User define V/F curve:
User can define 1st, 2nd , 3rd , 4th , 5th point of V/f curve percentage for output voltage reference, corresponding to
F1/F2/F3/F4/f frequency point separately. User also can define1st, 2nd , 3rd , 4th , 5th of frequency point to
correspond V1,V2, V3, V4, V5.
This parameter setting must satisfy the following conditions:
0
≤
F1
≤
F2
≤
F3
≤
F4
≤
F5
≤
maximum frequency upper limit; 0
≤
V1
≤
V2
≤
V3
≤
V4
≤
V5
≤
100%
H-01
User setting voltage V1
Range: 0.0%-[H-03]
Default: 3.0%
H-02
User setting frequency F1
Range : 0.00Hz-[H-04]
Default:1.00Hz
H-03
User setting voltage V2
Range:[H-01-H-05]
Default: 28.0%
H-04
User setting frequency F2
Range:[H-02-H-06] Default:
10.00Hz
H-05
User setting voltage V3
Range:[H-03-H-07]
Default: 55.0%
H-06
User setting frequency F3
Range:[H-04-H-08] Default:
25.00Hz
H-07
User setting voltage V4
Range:[H-05-H-09]
Default: 80.0%
H-08
User setting frequency F4
Range:[H-06-H-10] Default:
37.50Hz
H-09
User setting voltage V5
Range:[H-07]-100.0%
Default: 100.0%
H-10
User setting frequency F5
Range:[H-08]-maximum frequency
Default: 50.00Hz
V5
V4
V3
F
V5: 100%
F5: 50.00Hz
F2: 10.00Hz
Output voltage
Output frequency
User defines V/f curve schematic
V1: 3%
V2: 28%
V3: 55%
F3: 25.00Hz
V4: 80%
F4: 37.50Hz
F1: 1.00Hz
F
V1
V2
F
F
F