AC70 VC CONTROL FREQUENCY INVERTER MANUAL
APPENDIX
130
F-58
Input signal
characteristic selection
LED unit digit: VS1 input
characteristic selection
0: Positive characteristic
1: Negative characteristic
LED ten digit: AS input
characteristic selection
0: Positive characteristic
1: Negative characteristic
LED hundred digit: VS2 input
characteristic selection
0: Positive characteristic
1: Negative characteristic
LED thousand digit: Pulse input
characteristic selection
0: Positive characteristic
1: Negative characteristic
0000
●
105 23AH
F-59
Terminal analog input
filtering time constant
0.01-5.00
0.50
●
106
23BH
F-60
Output terminal
(
AO1
)
selection
0: Output signal disable
1: Output frequency/speed
2: Output current
3: Given frequency/speed
reference
4: PID given value
5: PID feedback value
6: DC bus voltage
7: Output voltage
1
●
106
23CH
F-61
Output terminal
(
AO2
)
selection
3
●
106
23DH
F-62
Analog output signal
selection
LED unit digit: A02 output signal
mode selection
0: Frequency pulse train output 1:
0-20mA
2: 4-20mA
3: 0-10V
LED ten digit: A01 output signal
mode selection
0: 0-10V
1: 0-20mA
2: 4-20mA
LED hundred digit: reserved
LED thousand digit: reserved
0003
●
107 23EH
F-63
AO1 output signal
gain
25%-200% 100%
●
107 23FH
F-64
AO2 output signal
gain
25%-200% 100%
●
107 240H
F-65
AO1 output signal zero
adjust
-10.0%-10.0% 0.0%
●
107 241H
F-66
AO2 output signal zero
adjust
-10.0%-10.0% 0.0%
●
107 242H