AC70 VC CONTROL FREQUENCY INVERTER MANUAL
APPENDIX
124
E-57 reserved
87
139H
E-58 reserved
87 13AH
E-59
Rotation speed display
scale factor
0.1-2000.0% 100.0%
●
87 13BH
E-60
Ratio of inverter output
voltage
50-110% 100%
〇
87 13CH
E-61
G/P type setting
0: G type 1: P type
0
〇
87
13DH
E-62
Speed search stabilizing
keeping time
0.200-10.000s 0.600s
●
87 13EH
E-63
Parameters change
protection
0: All the parameters changing is
allowed
1: Only keyboard digital given
parameter changing allowed
2: All the parameters prohibit
changing
0
●
88 13FH
E-64 Parameter
initialization
0: Null
1: Restores to factory default
setting value
2: Clear fault record
3: Transfer parameters of inverter
to keypad and save.
4: Transfer parameters saved of
keypad to inverter
0
〇
88 140H
E-65 Factory
password
0-9999
0
●
88 141H
E-66 Information
check
LED unit digit:
0: Null operation
1: State monitoring inquiry
2: Fault information inquiry
LED ten digit: LCD display
language
0:Chinese 1:English
0
●
88 142H
E-67
Interference suppression
selection
LED unit digit: Overvoltage
interference suppression
0: Disable 1: Enable
LED ten digital: SC interference
suppression
0: Disable
1: SC interference suppression 1
2: SC interference suppression 2
LED hundred digital: over
current interference
suppression
0: Disable
1: Over current interference
suppression 1
2: Over current interference
suppression 2
LED thousand digital: over
current in deceleration
suppression
0: Disable 1: Enable
2: Enable frequency reducing for
protecting over current.
0001
●
92 143H