AC70 VC CONTROL FREQUENCY INVERTER MANUAL
APPENDIX
121
E-15
Acceleration /deceleration
mode selection
LED unit digit: decelerate
/decelerate mode.
0: linear accelerate
1: S curve
LED tens digit:
Accelerate/decelerate time
datum point.
0: Motor rated frequency
1: Maximum frequency
LED hundreds digit:
Equidistance stop function
0: Disable
1: Enable
LED Thousands digit:
0: Disable
1: Enable
0000
●
74 10FH
E-16
Frequency given by digital
keypad
lower limit frequency - Upper limit
frequency
50.00Hz
●
76 110H
E-17
V/F curve mode
0: Constant torque curve
1: Descend torque curve(1.5 power
curve)
2: Descend torque curve(1.7
Power curve)
3: Descend torque curve(2.0
Square curve)
4: User define curve
0
〇
76 111H
E-18 Torque
boost
0.0%-25.0%
※
●
76 112H
E-19 Filter
time
constant
0.01-99.99
※
●
77 113H
E-20 Carrier
frequency
0.7KHz-15.0KHz
※
●
77 114H
E-21 Carrier
characteristic
LED unit Digit: Associate of
carrier frequency and output
frequency configure.
0: Output frequency associate is
disabled.
1: Output frequency associate is
enabled.
LED tens digit: Associate of
carrier frequency and module
temperature configure.
0: Module temperature associate is
disabled.
1: Module temperature associate is
enabled.
LED Hundreds digit: PWM mode
selection
0: Fixed PWM mode
2: Random PWM mode 1
LED Thousands digit:
Inhibition of shock
0: Inhibition of shock is disabled
1: Inhibition of shock is enabled
1010
●
77 115H
E-22
V/F slip compensation
0%-200%
100%
〇
78 116H