AC70 VC CONTROL FREQUENCY INVERTER MANUAL
FUNCTION PARAMETER DETAILED SPECIFICATION
106
input quantity
fmax
fmin
fmin
fmax
input lower
limit
limil
frequency
input upper
Relationship between frequency setting and input quantity
frequency
input lower
limit
input upper
limil
input quantity
F-59 Terminal analog input filtering
time constant
Range: 0.01-5.00s
Default: 0.50s
This is defined as the size of the input analog quantity signal filtering, for the purpose of eliminating the interference
signal. The longer filtering time is, the stronger anti-interfere ability is, but the respond speed slow down; The
shorter filter time is, the weaker anti-interfere ability is, but the respond speed become faster;
F-60 Output terminal(AO1)selection
Range: 0-7
Default: 1
F-61 Output terminal(AO2)selection Range:0-7
Default:
3
Output signal (A01) and (A02) mode is programmed by
[F-62]
0: Output signal disable
1: Output frequency/speed
2: Output current
3: Given frequency/speed reference
4: PID given value
5: PID feedback value
6: DC bus voltage
7: Output voltage
Tips: when (AO2
)
port is frequency pulse output or 4-20mA output, ‘0%’ corresponding output quantity is
not zero.