AC70 VC CONTROL FREQUENCY INVERTER MANUAL
FUNCTION PARAMETER DETAILED SPECIFICATION
75
Accel.time1
Decel.time1
Time
Time
Frequency
Motor
Decel time.1
Accl.time1
Linear accel./decel. fig.
Rated freq.
Motor
Rated freq.
Frequency
S curve accel./decel. fig.
LED tens digit: Accelerate/decelerate time datum point.
0: Motor rated frequency
Accelerate and decelerated time base on
[H-53]
motor rated frequency parameters
setting.
1: Maximum frequency
Accelerate and decelerated time base on
[H-09]
maximum frequency setting.
LED hundreds digit: Equidistant stop function
0: Disable
1: Enable
Equidistant stop function: Takes the maximum frequency deceleration time as datum line, the inverter stop rotation
running turns as same as the maximum frequency stop rotation turns after inverter performed stop command with
any frequency. For example, the maximum frequency is 60Hz, deceleration time is 1s. If the maximum frequency
decelerate stop rotation turns is 5, so the stop rotation turns also is 5 with 40Hz frequency given. The deceleration
time of equidistant stop during difference frequency given change as following curve diagram show.
Note: 1. This function is disabled when the frequency given less than10% of maximum frequency, the
inverter decelerate based on the deceleration time, it will not performed the equidistant function when the
frequency given less than 10% of maximum frequency.
2. The overvoltage and over current suppression occurs when the deceleration time is too short, the actual
of deceleration time will be longer, and the equidistant function can’t be performed.
LED Thousands digit:
0: Disable
1: Enable