AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
29
AC70-T3-500G/560P 1000A 2000A DCL-1200
------
------
AC70-T3-560G/630P ------ 2000A DCL-1200
------
------
Note: For DC reactor, input filter, output filter and other components specification details and circuit mode, please refer
chapter 7 “peripheral equipments and options”
Table 3-9: Suggested mains fittings for 3-phase 380V machine
Control loop terminals
●
Control loop terminals array
+10V
GND
X6
TB
TC
TA
A02
X1
X2
X5
VS1
COM
Y2
Y1
+24V
PLC
COM
PUL
A+
AS
GND
X3
X4
A01
VS2
B-
Sort
Terminal
Name
Function definition
Passive
connection
output
TA Normally-open
contact
Can set the action-object by programme.
Max contact capacity:3A/240VAC 5A/30VDC
TB Normally-closed
contact
TC
Common contact
State output
Y1
Collector open output 1
Can set the action-object by programme.
Max contact capacity:DC30V/50mA
Y2
Collector open output 2
Auxiliary
power supply
+24V
Auxiliary power
Max output: 24VDC/100mA.
COM
Auxiliary power output -
Multi-function
contact input
X1
Multi-function contact input 1
Build-in photoelectric converter can set the
action-object by program.
Input condition: Max DC30V/8mA.
Note:Factory setting is common-collector
characteristic input. If need common-emitter
characteristic input, please remove the short
connector b24V” and “PLC”, then use
the short connector to connect “PLC” and “COM”.
X2
Multi-function contact input 2
X3
Multi-function contact input 3
X4
Multi-function contact input 4
X5
Multi-function contact input 5
X6
Multi-function contact input 6
PLC
Multi-function
contact input common terminal
Pulse input
PUL
Pulse input
Pulse range:0.0
~
50.00kHz. Factory setting is
collector open output (R80,R82 transfer to
R81,R83 can be active input)