Table 16: M1.35 Multi-purpose
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.35.1
Control Mode
0
2
0
600
0 = U/f Freq Control
open loop
1 = Speed control open
loop
2 = Torque Control
open loop
1.35.2
Auto Torque Boost
0
1
0
109
0 = Disabled
1 = Enabled
1.35.3
Acceleration Time 2
0.1
300.0
s
10.0
502
1.35.4
Deceleration Time 2
0.1
300.0
s
10.0
503
1.35.5
Preset Frequency 1
P1.3
P1.4
Hz
5.0
105
1.35.6
U/f Ratio Select
0
2
0
108
0 = Linear
1 = Squared
2 = Programmable
1.35.7
Field Weakening
Point Frequency
8.00
P1.4
Hz
Varies
602
1.35.8
Voltage at Field
Weakening Point
10.00
200.00
%
100.00
603
1.35.9
U/f Midpoint Fre-
quency
0.0
P1.35.7
Hz
Varies
604
1.35.10
U/f Midpoint Voltage
0.0
100.00
%
100.0
605
1.35.11
Zero Frequency Volt-
age
0.00
40.00
%
Varies
606
1.35.12
Start Magnetizing
Current
0.00
Varies
A
Varies
517
1.35.13
Start Magnetizing
Time
0.00
600.00
s
0.00
516
1.35.14
DC Brake Current
Varies
Varies
A
Varies
507
0 = Disabled
1.35.15
DC Braking time at
stop
0.00
600.00
s
0.00
508
1.35.16
Frequency to start
DC braking at ramp
stop
0.10
50.00
%
0.00
515
QUICK STARTUP GUIDE
VACON · 45
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
1