Selection
number
Selection name
Description
0
Test 0% (Not used)
The analogue output is set to 0% or 20% so that it agrees
with parameter P3.5.4.1.3.
1
TEST 100%
The analogue output is set to 100% of the signal (10V /
20mA).
2
Output frequency
The actual output frequency from 0 to Maximum frequency
reference.
3
Frequency reference
The actual frequency reference from 0 to Maximum fre-
quency reference.
4
Motor speed
The actual motor speed from 0 to Motor nominal speed.
5
Output current
The output current of the drive from 0 to Motor nominal cur-
rent.
6
Motor torque
The actual motor torque from 0 to motor nominal torque
(100%).
7
Motor power
The actual motor power from 0 to Motor nominal power
(100%).
8
Motor voltage
The actual motor voltage from 0 to Motor nominal voltage.
9
DC-link voltage
The actual DC-link voltage 0…1000V.
10
PID Setpoint
The actual setpoint value of the PID Controller (0…100%).
11
PID Feedback
The actual feedback value of the PID Controller (0…100%).
12
PID output
The output of the PID controller (0…100%).
13
ExtPID output
The External PID controller output (0…100%).
14
Fieldbus Process Data In 1
Fieldbus Process Data In 1: 0…10000 (this agrees with 0…
100.00%).
15
Fieldbus Process Data In 2
Fieldbus Process Data In 2: 0…10000 (this agrees with 0…
100.00%).
16
Fieldbus Process Data In 3
Fieldbus Process Data In 3: 0…10000 (this agrees with 0…
100.00%).
17
Fieldbus Process Data In 4
Fieldbus Process Data In 4: 0…10000 (this agrees with 0…
100.00%).
18
Fieldbus Process Data In 5
Fieldbus Process Data In 5: 0…10000 (this agrees with 0…
100.00%).
19
Fieldbus Process Data In 6
Fieldbus Process Data In 6: 0…10000 (this agrees with 0…
100.00%).
20
Fieldbus Process Data In 7
Fieldbus Process Data In 7: 0…10000 (this agrees with 0…
100.00%).
PARAMETER DESCRIPTIONS
VACON · 265