Table 9: M1 Quick Setup
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.2
Application
0
5
2
212
0 = Standard
1 = Local/Remote
2 = Multi-Step Speed
3 = PID Control
4 = Multi-Purpose
5 = Motor Potentiome-
ter
1.3
Minimum Frequency
Reference
0.00
P1.4
Hz
0.0
101
1.4
Maximum Frequency
Reference
P1.3
320.0
Hz
50.0 /
60.0
102
1.5
Acceleration Time 1
0.1
300.0
s
5.0
103
1.6
Deceleration Time 1
0.1
300.0
s
5.0
104
1.7
Motor Current Limit
I
H
*0.1
I
S
A
Varies
107
1.8
Motor Type
0
2
0
650
0 = Induction Motor
1 = Permanent Magnet
Motor
2 = Reluctance Motor
1.9
Motor Nominal Volt-
age
Varies
Varies
V
Varies
110
Find this value U
n
on
the nameplate of the
motor.
NOTE!
Find out if the motor
connection is Delta or
Star.
1.10
Motor Nominal Fre-
quency
8.0
320.0
Hz
50 / 60
111
Find this value f
n
on
the nameplate of the
motor.
1.11
Motor Nominal
Speed
24
19200
Rpm
Varies
112
Find this value n
n
on
the nameplate of the
motor.
1.12
Motor Nominal Cur-
rent
I
H
* 0.1
I
H
* 2
A
Varies
113
Find this value I
n
on
the nameplate of the
motor.
1.13
Motor Cos Phi
(Power Factor)
0.30
1.00
Varies
120
Find this value on the
nameplate of the
motor.
VACON · 30
QUICK STARTUP GUIDE
1
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/