Table 38: Start/stop setup menu
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.2.6
I/O A Start/Stop
Logic
0
4
2 *
300
Logic = 0
Ctrl sgn 1 = Forward
Ctrl sgn 2 = Backward
Logic = 1
Ctrl sgn 1 = Forward
(edge)
Ctrl sgn 2 = Inverted
Stop
Ctrl sgn 3 = Bckwrd
(edge)
Logic = 2
Ctrl sgn 1 = Forward
(edge)
Ctrl sgn 2 = Bckwrd
(edge)
Logic = 3
Ctrl sgn 1 = Start
Ctrl sgn 2 = Reverse
Logic = 4
Ctrl sgn 1 = Start
(edge)
Ctrl sgn 2 = Reverse
P3.2.7
I/O B Start/Stop
Logic
0
4
2 *
363
See above.
P3.2.8
Fieldbus Start Logic
0
1
0
889
0 = A rising edge is
necessary
1 = State
P3.2.9
Start Delay
0.000
60.000
s
0.000
524
P3.2.10
Remote to Local
Function
0
2
2
181
0 = Keep Run
1 = Keep Run & Refer-
ence
2 = Stop
* = The selection of the application with parameter P1.2 Application gives the default value.
See the default values in Chapter 12 Appendix 1.