V2.8.4 PID OUTPUT (ID 23)
This monitoring value shows the output of the PID controller as a percentage (0-100%).
You can give this value to the motor control (frequency reference) or to an analogue output.
V2.8.5 PID STATUS (ID 24)
This monitoring value shows the state of the PID controller.
9.8
EXTERNAL PID CONTROLLER
V2.9.1 EXTPID SETPOINT (ID 83)
This monitoring value shows the value of the PID setpoint signal in process units.
You can use the parameter P3.14.1.10 to select the process unit (See 10.14.1 Basic settings).
V2.9.2 EXTPID FEEDBACK (ID 84)
This monitoring value shows the value of the PID feedback signal in process units.
You can use the parameter P3.14.1.10 to select the process unit (See 10.14.1 Basic settings).
V2.9.3 EXTPID ERROR (ID 85)
This monitoring value shows the error value of the PID controller.
The error value is the deviation of PID feedback from the PID setpoint in process unit.
You can use the parameter P3.14.1.10 to select the process unit (See 10.14.1 Basic settings).
V2.9.4 EXTPID OUTPUT (ID 86)
This monitoring value shows the output of the PID controller as a percentage (0-100%).
You can give this value to, for example, the analogue output.
V2.9.5 EXTPID STATUS (ID 87)
This monitoring value shows the state of the PID controller.
9.9
MULTI-PUMP
V2.10.1 MOTORS RUNNING (ID 30)
This monitoring value shows the actual number of motors that operate in the Multi-pump
system.
V2.10.2 AUTOCHANGE (ID 1114)
This monitoring value shows the status of the autochange requested.
VACON · 190
MONITORING VALUE DESCRIPTIONS