Table 16: M1.35 Multi-purpose
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.35.17
Load Drooping
0.00
50.00
%
0.00
620
1.35.18
Load Drooping Time
0.00
2.00
s
0.00
656
1.35.19
Load Drooping Mode
0
1
0
1534
0 = Normal; Load
drooping factor is con-
stant through the
whole frequency range
1 = Linear removal;
Load drooping is
removed linearly from
nominal frequency to
zero frequency
1.4.6
MOTOR POTENTIOMETER APPLICATION
Use the Motor potentiometer application for the processes where the frequency reference of
the motor is controlled (that is, increased and decreased) through digital inputs.
In this application, the I/O terminal is set to the default control place. the start/stop
commands are given with DI1 and DI2. The frequency reference of the motor is increased
with DI5 and decreased with DI6.
It is possible to configure all the drive outputs freely in all the applications. There are 1
analogue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the
basic I/O board.