Selection
number
Selection name
Description
21
Fieldbus Process Data In 8
Fieldbus Process Data In 8: 0…10000 (this agrees with 0…
100.00%).
22
Block Out.1
The output of the programmable Block 1: 0…10000 (this
agrees with 0…100.00%). See parameter menu M3.19 Drive
customizer.
23
Block Out.2
The output of the programmable Block 2: 0…10000 (this
agrees with 0…100.00%). See parameter menu M3.19 Drive
customizer.
24
Block Out.3
The output of the programmable Block 3: 0…10000 (this
agrees with 0…100.00%). See parameter menu M3.19 Drive
customizer.
25
Block Out.4
The output of the programmable Block 4: 0…10000 (this
agrees with 0…100.00%). See parameter menu M3.19 Drive
customizer.
26
Block Out.5
The output of the programmable Block 5: 0…10000 (this
agrees with 0…100.00%). See parameter menu M3.19 Drive
customizer.
27
Block Out.6
The output of the programmable Block 6: 0…10000 (this
agrees with 0…100.00%). See parameter menu M3.19 Drive
customizer.
28
Block Out.7
The output of the programmable Block 7: 0…10000 (this
agrees with 0…100,00%). See parameter menu M3.19 Drive
customizer.
29
Block Out.8
The output of the programmable Block 8: 0…10000 (this
agrees with 0…100.00%). See parameter menu M3.19 Drive
customizer.
30
Block Out.9
The output of the programmable Block 9: 0…10000 (this
agrees with 0…100.00%). See parameter menu M3.19 Drive
customizer.
31
Block Out.10
The output of the programmable Block 10: 0…10000 (this
agrees with 0…100.00%). See parameter menu M3.19 Drive
customizer.
P3.5.4.1.2 AO1 FILTER TIME (ID 10051)
Use this parameter to set the filtering time for the analog signal.
The filtering function is disabled when the filtering time is 0. See P3.5.2.1.2.
P3.5.4.1.3 AO1 MINIMUM (ID 10052)
Use this parameter to change the range of the analogue output signal.
For example, if '4mA' is selected, the range of analogue output signal is 4..20mA.
Select the signal type (current/voltage) with the dip switches. The analogue output scaling is
different in P3.5.4.1.4. See also P3.5.2.1.3.
VACON · 266
PARAMETER DESCRIPTIONS