GROUP 3.14: EXTERNAL PID CONTROLLER
Table 95: Basic settings for the external PID controller
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.14.1.1
Enable External PID
0
1
0
1630
0 = Disabled
1 = Enabled
P3.14.1.2
Start Signal
DigIN
Slot0.2
1049
OPEN = PID2 in stop
mode
CLOSED = PID2 regu-
lating
P3.14.1.3
Output in Stop
0.0
100.0
%
0.0
1100
P3.14.1.4
PID Gain
0.00
1000.00
%
100.00
1631
See P3.13.1.1
P3.14.1.5
PID Integration Time
0.00
600.00
s
1.00
1632
See P3.13.1.2
P3.14.1.6
PID Derivation Time
0.00
100.00
s
0.00
1633
See P3.13.1.3
P3.14.1.7
Process Unit Selec-
tion
0
37
0
1635
See P3.13.1.4
P3.14.1.8
Process Unit Min
Varies
Varies
Varies
0
1664
See P3.13.1.5
P3.14.1.9
Process Unit Max
Varies
Varies
Varies
100
1665
See P3.13.1.6
P3.14.1.10
Process Unit Deci-
mals
0
4
2
1666
See P3.13.1.7
P3.14.1.11
Error Inversion
0
1
0
1636
See P3.13.1.8
P3.14.1.12
Dead Band
Varies
Varies
Varies
0.0
1637
See P3.13.1.9
P3.14.1.13
Dead Band Delay
0.00
320.00
s
0.00
1638
See P3.13.1.10
VACON · 152