Table 39: Frequency reference parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.3.1.7
Keypad Control Ref-
erence Selection
0
19
2 *
121
0 = Preset Frequency 0
1 = Keypad
2 = Fieldbus
3 = AI1
4 = AI2
5 = AI1+AI2
6 = PID reference
7 = Motor potentiome-
ter
8 = Joystick
9 = Jogging reference
10 = Block Out.1
11 = Block Out.2
12 = Block Out.3
13 = Block Out.4
14 = Block Out.5
15 = Block Out.6
16 = Block Out.7
17 = Block Out.8
18 = Block Out.9
19 = Block Out.10
P3.3.1.8
Keypad Reference
P3.3.1.1 P3.3.1.2.
Hz
0.00
184
P3.3.1.9
Keypad Direction
0
1
0
123
0 = Forward
1 = Reverse
P3.3.1.10
Fieldbus Control
Reference Selection
0
19
3 *
122
0 = Preset frequency 0
1 = Keypad
2 = Fieldbus
3 = AI1
4 = AI2
5 = AI1+AI2
6 = PID reference
7 = Motor potentiome-
ter
8 = Joystick
9 = Jogging reference
10 = Block Out.1
11 = Block Out.2
12 = Block Out.3
13 = Block Out.4
14 = Block Out.5
15 = Block Out.6
16 = Block Out.7
17 = Block Out.8
18 = Block Out.9
19 = Block Out.10
* = The selection of the application with parameter P1.2 Application gives the default value.
See the default values in Chapter 12 Appendix 1.
VACON · 108
PARAMETERS MENU
5
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/