1
Language selection (P6.1)
The selection is different in all the language
packages
2
Daylight saving* (P5.5.5)
Russia
US
EU
OFF
3
Time* (P5.5.2)
hh:mm:ss
4
Year* (P5.5.4)
yyyy
5
Date* (P5.5.3)
dd.mm.
* If a battery is installed, you see these steps.
6
Run Startup wizard?
Yes
No
To set the parameter values manually, make the selection No and push the OK button.
7
Make a selection of an application (P1.2 Application,
ID212)
Standard
Local/Remote
Multi-step speed
PID control
Multi-purpose
Motor potentiometer
8
Set a value for P3.1.2.2 Motor Type (so that it agrees
with the nameplate)
PM motor
Induction motor
Reluctance motor
9
Set a value for P3.1.1.1 Motor Nominal Voltage (so
that it agrees with the nameplate)
Range: Varies
10
Set a value for P3.1.1.2 Motor Nominal Frequency
(so that it agrees with the nameplate)
Range: 8.00...320.00 Hz
11
Set a value for P3.1.1.3 Motor Nominal Speed (so
that it agrees with the nameplate)
Range: 24...19200
12
Set a value for P3.1.1.4 Motor Nominal Current
Range: Varies
13
Set a value for P3.1.1.5 Motor Cos Phi
Range: 0.30-1.00
If you set Motor Type to Induction Motor, you see the next step. If your selection is PM Motor,
the value of parameter P3.1.1.5 Motor Cos Phi is set to 1.00 and the wizard goes directly to
step 14.
VACON · 14
QUICK STARTUP GUIDE
1
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/