Jogging Ref 1
Output
Frequency
[Hz]
Jogging Ref 2
Jogging Ref 2 Activation
(Digital input signal)
Jogging Ref 1 Activation
(Digital input signal)
Enable DI Jogging
(Digital input signal)
Jogging Ramp
Fieldbus Control Word Bit 11
Fieldbus Control Word Bit 10
Fig. 39: The Jogging parameters
P3.3.6.1 ENABLE DI JOGGING (ID 532)
Use this parameter to enable the jogging commands from digital inputs.
This parameter gives the digital input signal that is used to enable jogging commands from
digital inputs. This signal does not have an effect on the jogging commands that come from
Fieldbus.
P3.3.6.2 JOGGING REFERENCE 1 ACTIVATION (ID 530)
Use this parameter to set the digital input signals for the Jogging function activation.
This parameter gives the digital input signal that is used to set the frequency reference for
Jogging function and make the drive start. You can use this digital input signal only when
Enable DI Jogging is active.
NOTE!
If you activate Enable DI Jogging and this digital input, the drive starts.
NOTE!
If the 2 activation signals are active at the same time, the drive stops.
P3.3.6.3 JOGGING REFERENCE 2 ACTIVATION (ID 531)
Use this parameter to set the digital input signals for the Jogging function activation.
This parameter gives the digital input signal that is used to set the frequency reference for
Jogging function and make the drive start. You can use this digital input signal only when
Enable DI Jogging is active.
NOTE!
If you activate Enable DI Jogging and this digital input, the drive starts.
VACON · 234
PARAMETER DESCRIPTIONS