5.17
GROUP 3.17: FIRE MODE
Table 102: Fire mode parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.17.1
Fire Mode Password
0
9999
0
1599
1002 = Enabled
1234 = Test mode
P3.17.2
Fire Mode Frequency
Source
0
18
0
1617
0 = Fire Mode fre-
quency
1 = Preset speeds
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1 + AI2
7 = PID1
8 = Motor potentiome-
ter
9 = Block Out.1
10 = Block Out.2
11 = Block Out.3
12 = Block Out.4
13 = Block Out.5
14 = Block Out.6
15 = Block Out.7
16 = Block Out.8
17 = Block Out.9
18 = Block Out.10
P3.17.3
Fire Mode Frequency
0.00
P3.3.1.2
Hz
50.00
1598
P3.17.4
Fire Mode Activation
on OPEN
DigIN
Slot0.2
1596
OPEN = Fire Mode
active
CLOSED = No action
P3.17.5
Fire Mode Activation
on CLOSE
DigIN
Slot0.1
1619
OPEN = No action
CLOSED = Fire Mode
active
P3.17.6
Fire Mode Reverse
DigIN
Slot0.1
1618
OPEN = Forward
CLOSED = Reverse
DigIN Slot0.1 = For-
ward
DigIN Slot0.2 = Reverse
V3.17.7
Fire Mode Status
0
3
1597
0 = Disabled
1 = Enabled
2 = Activated (Enabled
+ DI Open)
3 = Test Mode
V3.17.8
Fire Mode Counter
0
65535
1679
VACON · 158
PARAMETERS MENU
5