5.6
GROUP 3.6: FIELDBUS DATA MAPPING
Table 61: Fieldbus data mapping
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.6.1
Fieldbus Data Out 1
Selection
0
35000
1
852
P3.6.2
Fieldbus Data Out 2
Selection
0
35000
2
853
P3.6.3
Fieldbus Data Out 3
Selection
0
35000
3
854
P3.6.4
Fieldbus Data Out 4
Selection
0
35000
4
855
P3.6.5
Fieldbus Data Out 5
Selection
0
35000
5
856
P3.6.6
Fieldbus Data Out 6
Selection
0
35000
6
857
P3.6.7
Fieldbus Data Out 7
Selection
0
35000
7
858
P3.6.8
Fieldbus Data Out 8
Selection
0
35000
37
859
Table 62: The default values for Process Data Out in fieldbus
Data
Default value
Scale
Process Data Out 1
Output frequency
0.01 Hz
Process Data Out 2
Motor speed
1 rpm
Process Data Out 3
Motor current
0.1 A
Process Data Out 4
Motor torque
0.1%
Process Data Out 5
Motor power
0.1%
Process Data Out 6
Motor voltage
0.1 V
Process Data Out 7
DC link voltage
1 V
Process Data Out 8
Last active fault code
1
For example, the value 2500 for Output frequency equals 25.00 Hz, because the scale is 0.01.
All the monitoring values that you can find in Chapter 4.1 Monitor group are given the scale
value.
PARAMETERS MENU
VACON · 127