P3.2.1 REMOTE CONTROL PLACE (ID 172)
Use this parameter to select the remote control place (start/stop).
Use this parameter to change back to remote control from VACON
®
Live, for example if the
control panel is broken.
P3.2.2 LOCAL/REMOTE (ID 211)
Use this parameter to switch between the local and remote control places.
Local control place is always keypad control. The remote control place can be I/O or
Fieldbus, depending on the 'Remote Control Place' parameter value.
P3.2.3 KEYPAD STOP BUTTON (ID 114)
Use this parameter to enable the keypad stop button.
When this function is enabled, a press of keypad stop button always stops the drive
(regardless of the control place). When this function is disabled, a press of keypad stop
button stops the drive in local control only.
Selection
number
Selection name
Description
0
Yes
The keypad stop button is always enabled.
1
No
Limited function of the keypad stop button.
P3.2.4 START FUNCTION (ID 505)
Use this parameter to select the type of the start function.
Selection
number
Selection name
Description
0
Ramping
The drive accelerates from 0 frequency to frequency refer-
ence.
1
Flying start
The drive detects the actual speed of the motor and acceler-
ates from that speed to frequency reference.
P3.2.5 STOP FUNCTION (ID 506)
Use this parameter to select the type of the stop function.
Selection
number
Selection name
Description
0
Coasting
The motor stops on its inertia. When the stop command is
given, the control by the drive stops and the current from the
drive goes to 0.
1
Ramp
After the stop command, the speed of the motor is decreased
to zero speed according to the deceleration parameters.