1
Set a value for P3.1.2.2 Motor Type (so that it agrees
with the nameplate of the motor)
PM motor
Induction motor
Reluctance motor
2
Set a value for P3.1.1.1 Motor Nominal Voltage (so
that it agrees with the nameplate of the motor)
Range: Varies
3
Set a value for P3.1.1.2 Motor Nominal Frequency
(so that it agrees with the nameplate of the motor)
Range: 8.00…320.00 Hz
4
Set a value for P3.1.1.3 Motor Nominal Speed (so
that it agrees with the nameplate of the motor)
Range: 24…19200 rpm
5
Set a value for P3.1.1.4 Motor Nominal Current (so
that it agrees with the nameplate of the motor)
Range: Varies
If you set Motor Type to Induction Motor, you see the next step. If your selection is PM Motor,
the value of parameter P3.1.1.5 Motor Cos Phi is set to 1.00, and the wizard goes directly to
step 7.
6
Set a value for P3.1.1.5 Motor Cos Phi (so that it
agrees with the nameplate of the motor)
Range: 0.30…1.00
7
Set a value for P3.3.1.1 Minimum Frequency Refer-
ence
Range: 0.00 Hz…P3.3.1.2
8
Set a value for P3.3.1.2 Maximum Frequency Refer-
ence
Range: P3.3.1.1…320.00 Hz
9
Set a value for P3.4.1.2 Acceleration Time 1
Range: 0.1…300.0 s
10
Set a value for P3.4.1.3 Deceleration Time 1
Range: 0.1…300.0 s
11
Make a selection of a control place (where you give
the start/stop commands)
I/O Terminal
Fieldbus
Keypad
12
Set a value for P3.13.1.4 Process Unit Selection
More than 1 selection
If your selection is other than %, you see the next steps. If your selection is %, the wizard
goes directly to step 17.
13
Set a value for P3.13.1.5 Process Unit Min
The range depends on the selection in step
12.
14
Set a value for P3.13.1.6 Process Unit Max
The range depends on the selection in step
12.
15
Set a value for P3.13.1.7 Process Unit Decimals
Range: 0…4
16
Set a value for P3.13.3.3 Feedback 1 Source Selec-
tion
See the table Feedback settings in Chapter
5.13 Group 3.13: PID controller
WIZARDS
VACON · 57