NOTE!
This parameter is not available if there is no option board for temperature
measurement.
10.20
DRIVE CUSTOMIZER
P3.19.1 OPERATION MODE (ID 15001)
Use this parameter to select the operation mode of the drive customizer.
When 'Programming' is selected, the execution of the block program is stopped and outputs
of the each function block are 0. When 'Execute Program' is selected, the block program is
executed and block outputs are updated normally. The Drive Customizer can not be
configured when 'Execute Program' is selected.
Please use the graphical Drive Customizer tool in VACON
®
Live.
10.21
MECHANICAL BRAKE
You can monitor the mechanical brake with the monitoring value Application Status Word 1
in the monitoring group Extras and advanced.
The Mechanical brake control function controls an external mechanical brake with a digital
output signal. The mechanical brake is opened/closed when the drive output frequency
breaks the opening/closing limits.
P3.20.1 BRAKE CONTROL (ID 1541)
Use this parameter to set the operation mode of the mechanical brake.
Mechanical brake status can be supervised via digital input when mode 2 is selected.
Table 127: The selection of the operation mode of the mechanical brake
Selection
number
Selection name
Description
0
Disabled
The mechanical brake control is not used.
1
Enabled
The mechanical brake control is used, but there is no super-
vision of the brake status.
2
Enabled with brake status
supervision
The mechanical brake control is used, and a digital input sig-
nal monitors the brake status (P3.20.8).
VACON · 322
PARAMETER DESCRIPTIONS
10