Table 9: Drive fuses, 380-500 V, Mersen (IEC)
Frame
Type
I
L
[A]
Catalogue number of the
fuse
Fuse
rating
[A]
Number
of fuses
needed
Fuse
size
Minimum
prospective
short
circuit
current [A]
MR8
0140 5
140
NH1UD69V250PV
250
3
1
1400
0170 5
170
NH1UD69V350PV
350
3
1
2400
0205 5
205
NH1UD69V400PV
400
3
1
2800
MR9
0261 5
261
NH2UD69V500PV
500
3
2
3300
0310 5
310
NH2UD69V630PV
630
3
2
5000
MR10
0385 5
385
NH2UD69V700PV
700
3
2
5700
0460 5
460
NH3UD69V900PV
900
3
3
7000
0520 5
520
NH3UD69V1000PV
1000
3
3
8600
0590 5
590
PC73UD90V10CPA
1000
3
3
13000
MR12
0650 5
650
NH2UD69V630PV
630
6
2
5000
0730 5
730
NH2UD69V700PV
700
6
2
5700
0820 5
820
NH3UD69V900PV
900
6
3
7000
0920 5
920
NH3UD69V1000PV
1000
6
3
8600
1040 5
1040
NH3UD69V1000PV
1000
6
3
8600
1180 5
1180
PC73UD90V10CPA
1000
6
3
13000
POWER CABLING