Table 29: The minimum resistance and the brake power, mains voltage
525-690 V
Frame
The minimum brake
resistance [Ω]
Brake power* @1166 VDC
[kW]
MR8
9
110
MR9
7
193
MR10
2.5
400
MR12
2 x 2.5 **
800
* = When you use recommended resistor types.
** = The MR12 must have 2 brake resistors.
VACON · 98
TECHNICAL DATA, VACON® 100