9.2
VACON
®
100 FLOW - TECHNICAL DATA
Table 33: The technical data of the Vacon
®
100 FLOW AC drive
Technical item or function
Technical data
Mains connection
Input voltage U
in
380-500 V, 525-690 V, -10%...+10%
Input frequency
50-60 Hz, -5...+10%
Connection to mains
Once per minute or less frequently
Starting delay
8 s (MR8 to MR12)
Mains
•
Mains types: TN, TT, and IT
•
Short circuit current: the maximum short circuit
current must be < Icc 65 kA.
Motor connection
Output voltage
0-U
in
Continuous output current
I
L
: Ambient temperature max. +40 °C overload 1.1 x I
L
(1 min/10 min)
Output frequency
0-320 Hz (standard)
Frequency resolution
0.01 Hz
VACON · 106
TECHNICAL DATA, VACON® 100 FLOW
9
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Summary of Contents for 100 INDUSTRIAL
Page 1: ...vacon 100 ac drives installation manual enclosed drives ...
Page 2: ......
Page 4: ...VACON 4 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Page 115: ......