Table 23: The maintenance intervals and tasks
Maintenance interval
Maintenance task
Regularly
Do a check of the tightening torques of the terminals.
Do a check of the filters.
6-24 months (The interval is different in different envi-
ronments.)
Do a check of the mains and motor cable terminals
and the control terminals.
Make sure that the cooling fan operates correctly.
Make sure that there is no corrosion on the terminals,
the busbars or other surfaces.
Do a check of the door filters of the cabinet.
Do a check of the internal filter of the power unit.
24 months (The interval is different in different envi-
ronments.)
Clean the heatsink and the cooling tunnel.
6-10 years
Replace the main fan.
Replace the internal fans if the drive has them.
Replace the fan power supply.
10 years
Replace the battery of the RTC. The battery is optional.
This table is valid for Vacon components. To do maintenance on components that are made
by other manufacturers, obey the manual of the component in question.