9.1.2
MAINS VOLTAGE 525-690 V
Table 32: The power ratings of Vacon
®
100 FLOW in mains voltage 525-690 V, 50-60 Hz, 3~
Frame
Drive type
Loadability
Motor shaft power
Continuous
current
I
Lout
[A]
Input
current I
Lin
[A]
10%
overload
current [A]
Max
current I
S
2s
600 V
mains
690 V
mains
10%
overload
40°C [hp]
10%
overload
40°C [kW]
MR8
0080
80.0
90.0
88.0
124.0
75.0
55.0
0100
100.0
106.0
110.0
160.0
100.0
75.0
0125
125.0
127.0
137.5
200.0
125.0
90.0
MR9
0144
144.0
156.0
158.4
250.0
150.0
110.0
0170
170.0
179.0
187.0
288.0
-
132.0
0208
208.0
212.0
228.8
340.0
200.0
160.0
MR10
0261
261.0
272.0
287.1
416.0
250.0
200.0
0325
325.0
330.0
357.5
522.0
300.0
250.0
0385
385.0
386.0
423.5
650.0
400.0
315.0
0416*
416.0
415.0
457.6
770.0
450.0
355.0
MR12
0460
460.0
477.0
506.0
832.0
450.0
400.0
0520
520.0
532.0
572.0
920.0
500.0
450.0
0590
590.0
597.0
649.0
1040.0
600.0
500.0
0650
650.0
653.0
715.0
1180.0
650.0
560.0
0750*
750.0
747.0
825.0
1300.0
700.0
630.0
0820*
820.0
813.0
902.0
1300.0
800.0
630.0
* = The maximum ambient temperature is 35°C with the du/dt filter option. These currents
are not available when you have the options back channel cooling and du/dt filter (+CHCB
and +PODU).
TECHNICAL DATA, VACON® 100 FLOW
VACON · 105
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]