The requirements: +CAPU Auxiliary AC supply terminals or +CAPT Auxiliary voltage
transformer
N
L
1
-XD1
-XD1
-FCC
2 A
-EA1
5W
Fig. 11: The cabinet light
+CAPT: AUXILIARY VOLTAGE TRANSFORMER
This option provides the supply of auxiliary voltage for other options. The supply for the
auxiliary transformer is taken from mains. If you use the option AC fuses and fuse switch
(+CIFD), the supply for the auxiliary voltage transformer is taken from between the drive and
the fuse switch. This means that the control voltage is disconnected with the main switch.
The requirements: Not +CAPU Auxiliary AC supply terminals
2
2
4 A
1
I>
3
-TA4
L1-L2
-FC6
-FC4
-XD1
Fig. 12: The auxiliary voltage transformer
+CAPD: 24 VDC POWER SUPPLY
This option provides a backup supply for the control unit of the drive. Use it also for other
auxiliary options for which a 24 VDC supply is necessary.
The requirements: +CAPU Auxiliary AC supply terminals or +CAPT Auxiliary voltage
transformer. The backup supply for the control unit reCAPU Auxiliary AC supply
terminals.
L
1
AC
AC
N
-
+
-XD1
-FC7
2 A
-TB7
24 V
60 W
-XD1
-XD3
Fig. 13: The 24 VDC power supply
+CAPS: AC CUSTOMER SOCKET
The socket provides a power supply for your measurement equipment, tools or computer.
The default voltage is 230 VAC, and 115 VAC in the North American regional variant. The
maximum output power with 230 VAC is 450 VA and with 115 VAC it is 230 VA when an
external supply (+CAPU) is used, and 180 VA when a transformer supply (+CAPT) is used.
VACON · 26
MOUNTING
4